Uplift check (UPL)

The check verifies that the foundation is not lifted by the water uplift pressure when the water table reaches its maximum level. It is opened from the calculation tab, settlements group, with the Uplift check (UPL) button. The stratigraphy, the foundation and the water table must be defined: the button is enabled only if the project has a water table (in Stratigraphy, field Water table depth, or with the Ground Water Table command).

Code references: EN 1997-1 par. 2.4.7.4 and Table A.15; NTC 2018 (Italy) par. 6.2.3.2 and Table 6.2.III. The program uses the code selected in the general data of the project.

Verification condition

\[ V_{dst,d} \le G_{stb,d} + R_d \]

with

\[ V_{dst,d} = \gamma_{G,dst} \cdot \gamma_w \cdot h_w \cdot A \qquad h_w = D - z_w \qquad G_{stb,d} = \gamma_{G1} \cdot G_1 + \gamma_{G2} \cdot G_2 \]

where:

  • \( h_w \) water height above the foundation level, with \( D \) depth of the foundation level and \( z_w \) depth of the project water table below ground level, to be set at its maximum level (if the water table is below the foundation level there is no uplift; a negative value means water above ground level);
  • \( A \) foundation base area;
  • \( G_1 \), \( G_2 \) stabilising permanent actions, structural (structure and foundation) and non-structural;
  • \( R_d \) any additional design resistances (side friction, anchors...), already divided by their partial factors.

The program also reports the safety factor \( (G_{stb,d} + R_d) / V_{dst,d} \). In the report and in the window the destabilising action is labelled Vinst,d.

Data

Data Notes
Run the uplift check enables the check and its section in the report
Water table depth below ground level (maximum level) it is the project water table: changing it here, with OK it is updated also in Stratigraphy and in the drawing
Unit weight of water default 10 kN/m³
Foundation base area 0 = foundation area (B × L, or circle)
G1, G2 stabilising permanent actions, in kN
Rd additional design resistances, in kN

Partial factors

The factors are read from the file of the project code (Standards_Geo folder, GFA_UPL section) and can be edited. The Code values button resets them to those of the file.

Code Uplift \( \gamma_{G,dst} \) \( \gamma_{G1} \) stabilising \( \gamma_{G2} \) stabilising
EN 1997-1 (Table A.15), also SR EN 1997-1 1.0 0.9 0.9
NTC 2018 (Table 6.2.III) 1.1 0.9 0.8

Example

Raft 8 × 10 m, foundation level at 3 m, maximum water table at 1 m below ground level, EN 1997-1, \( G_1 \) = 4000 kN, \( G_2 \) = 500 kN:

  • \( h_w = 3 - 1 = 2 \) m, \( A = 80 \) m²
  • \( V_{dst,d} = 1.0 \cdot 10 \cdot 2 \cdot 80 = 1600 \) kN
  • \( G_{stb,d} = 0.9 \cdot 4000 + 0.9 \cdot 500 = 4050 \) kN
  • safety factor 4050 / 1600 = 2.53: satisfied

Results

The window updates the results while the data are edited. With OK the data are saved in the project and, if the check is enabled, the calculation report contains the section Uplift check (UPL) with the code reference, the data, the factors and the result.